Instrumentation Cables 

   EN 50288-7 Instrumentation Cables
XLPE Insulated, LS ZH Sheathed & Overall Screened Instrumentation Cables (Multitriple)
RE-2X(St)H 90°C / 300 V

EN 50288-7 Instrumentation Cables

STANDARDS
Basic design to EN 50288-7

Applications
These cables are used for transmission of analoge and digital signals in instrument and control systems at chemistry and petrochemistry industry plants, power plants, natural gas and petroluem plants, etc...
These cables are used in the environments which have no corrosive gases are emitted in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. Instrumentation cables are not allowed for direct connection to a low impedance sources, e.g. public mains electricity supply. With blue sheath it is suitable for intrinsically safe systems. These cables are not recommended for direct burial. They are for indoor and outdoor installation, in dry and wet locations; on racks, trays, in conduits.

FIRE PERFORMANCE

Flame Retardance (Single Vertical
Wire Test)
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE
0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation
(Vertically-mounted bundled wires
& cable test)***
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen Free IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas Emission IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke Emission IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gases NES 02-713; NF C 20-454
Sunlight Resistance UL 1581 section 1200
Oil Resistance** ICEA S-73-532
Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min
60% of tensile strength/min.60% of elongation, *** denotes optional
.

VOLTAGE RATING
300V

CABLE CONSTRUCTION
Conductor: Annealed copper solid or plain copper stranded to IEC 60228 Class 2.
Insulation: Extruded cross-linked XLPE compound, EN 50290. 2-29.
Triple: Three conductors twisted to form a triple
Lay-up: Triples laid up in layers of optimum pitch
Separator: Polyester tape
Overall Screen: Aluminium/polyester tape with tinned copper drain wire, 0.5mm2
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

COLOUR CODE
Insulation: Black / White / Red, continuously numbered on white core(1, 2..)for multitriples.
Outer Sheath: Black or blue for intrinsically safe systems

Physical AND THERMAL PROPERTIES
Temperature Range During Operation (Fixed State): -30°C – +90°C
Temperature Range During Installation (Mobile State): -5°C – +50°C
Minimum Bending Radius: 7.5 X Overall Diameter

CONSTRUCTION PARAMETERS

Caledonian Cable Code RE-2X(St)H
No. of Triples x3xCross Section Nominal Insulation Thickness Nominal Outer Sheath Thickness Nominal Overall Diameter Approx. Weight

 

No.x3xmm2 mm mm mm kg/km
0.5mm2 , Multi-striple
RE-2X(St)H 2T0.5 2x3x0,50 0.35 0.9 8.4 91
RE-2X(St)H 4T0.5 4x3x0,50 0.35 1.0 9.8 123
RE-2X(St)H 5T0.5 5x3x0,50 0.35 1.0 10.8 155
RE-2X(St)H 6T0.5 6x3x0,50 0.35 1.0 12.1 185
RE-2X(St)H 8T0.5 8x3x0,50 0.35 1.1 13.1 221
RE-2X(St)H 10T0.5 10x3x0,50 0.35 1.1 14.7 275
RE-2X(St)H 12T0.5 12x3x0,50 0.35 1.1 15.2 316
RE-2X(St)H 16T0.5 16x3x0,50 0.35 1.2 17.4 414
RE-2X(St)H 20T0.5 20x3x0,50 0.35 1.2 19.1 508
RE-2X(St)H 24T0.5 24x3x0,50 0.35 1.3 20.9 594
0.75mm2 , Multi-striple
RE-2X(St)H 2T0.75 2x3x0,75 0.38 0.9 9.3 114
RE-2X(St)H 4T0.75 4x3x0,75 0.38 1.0 10.9 163
RE-2X(St)H 5T0.75 5x3x0,75 0.38 1.0 12.0 199
RE-2X(St)H 6T0.75 6x3x0,75 0.38 1.1 13.7 245
RE-2X(St)H 8T0.75 8x3x0,75 0.38 1.1 14.7 296
RE-2X(St)H 10T0.75 10x3x0,75 0.38 1.2 16.7 366
RE-2X(St)H 12T0.75 12x3x0,75 0.38 1.2 17.3 423
RE-2X(St)H 16T0.75 16x3x0,75 0.38 1.3 19.7 555
RE-2X(St)H 20T0.75 20x3x0,75 0.38 1.3 21.7 681
RE-2X(St)H 24T0.75 24x3x0,75 0.38 1.4 23.7 802
1.0mm2 , Multi-striple
RE-2X(St)H 2T1.0 2x3x1 0.4 1.0 10.4 135
RE-2X(St)H 4T1.0 4x3x1 0.4 1.0 11.9 202
RE-2X(St)H 5T1.0 5x3x1 0.4 1.0 13.2 251
RE-2X(St)H 6T1.0 6x3x1 0.4 1.1 15.0 303
RE-2X(St)H 8T1.0 8x3x1 0.4 1.1 16.1 379
RE-2X(St)H 10T1.0 10x3x1 0.4 1.2 18.4 461
RE-2X(St)H 12T1.0 12x3x1 0.4 1.2 19.0 544
RE-2X(St)H 16T1.0 16x3x1 0.4 1.3 21.7 717
RE-2X(St)H 20T1.0 20x3x1 0.4 1.4 24.1 880
RE-2X(St)H 24T1.0 24x3x1 0.4 1.4 26.1 1048
1.3mm2 , Multi-striple
RE-2X(St)H 2T1.3 2x3x1,3 0.45 1.0 11.5 175
RE-2X(St)H 4T1.3 4x3x1,3 0.45 1.1 13.4 258
RE-2X(St)H 5T1.3 5x3x1,3 0.45 1.1 14.8 318
RE-2X(St)H 6T1.3 6x3x1,3 0.45 1.2 16.9 387
RE-2X(St)H 8T1.3 8x3x1,3 0.45 1.2 18.1 474
RE-2X(St)H 10T1.3 10x3x1,3 0.45 1.3 20.7 589
RE-2X(St)H 12T1.3 12x3x1,3 0.45 1.3 21.4 695
RE-2X(St)H 16T1.3 16x3x1,3 0.45 1.4 24.4 918
RE-2X(St)H 20T1.3 20x3x1,3 0.45 1.5 27.1 1124
RE-2X(St)H 24T1.3 24x3x1,3 0.45 1.6 29.6 1336
1.5mm2 , Multi-striple
RE-2X(St)H 2T1.5 2x3x1,5 0.45 1.0 11.9 191
RE-2X(St)H 4T1.5 4x3x1,5 0.45 1.1 14.0 287
RE-2X(St)H 5T1.5 5x3x1,5 0.45 1.1 15.4 355
RE-2X(St)H 6T1.5 6x3x1,5 0.45 1.2 17.6 432
RE-2X(St)H 8T1.5 8x3x1,5 0.45 1.3 19.1 540
RE-2X(St)H 10T1.5 10x3x1,5 0.45 1.3 21.6 672
RE-2X(St)H 12T1.5 12x3x1,5 0.45 1.4 22.5 779
RE-2X(St)H 16T1.5 16x3x1,5 0.45 1.5 25.7 1031
RE-2X(St)H 20T1.5 20x3x1,5 0.45 1.6 28.6 1265
RE-2X(St)H 24T1.5 24x3x1,5 0.45 1.7 31.1 1508
Note : Other conductor sizes & core configurations are available upon request.

Electrical PROPERTIES

Conductor Area Size mm 2 0.5 0.75 1.0 1.3 1.5
Insulation thickness (nominal) mm 0.35 0.38 0.4 0.45 0.45
Conductor resistance (20°C) Ω/km 36.7 25.0 18.5 14.2 12.3
Insulation resistance (20°C) MΩ.km(Min.) 5000
Mutual Capacitance (1 kHz) up to 4 trples pF/m(Max.) 90 90 90 102 102

 

above 4 trples pF/m(Max.) 75 75 75 85 85
Inductance mH/km(Max.) 1
L / R (ratio) (max.) μH/Ω 25 25 25 40 40
Operating voltage V 300
Test Voltage Urms Core to Core V 1500
Core to Screen V 1500